	<title>marine-ac.com&#187; boat ac troubleshooting</title>
	<atom:link href="http://marine-ac.com/tag/boat-ac-troubleshooting/feed/" rel="self" type="application/rss+xml" />
	<link>http://marine-ac.com</link>
	<description>Marine Air Conditioning</description>
	<lastBuildDate>Sat, 04 Feb 2012 23:56:32 +0000</lastBuildDate>
	<language>en</language>
	<sy:updatePeriod>hourly</sy:updatePeriod>
	<sy:updateFrequency>1</sy:updateFrequency>
	<generator>http://wordpress.org/?v=3.3.1</generator>
		<item>
		<title>Marine A/C before Cruisair or Marine Air</title>
		<link>http://marine-ac.com/marine-ac-cruisair-marine-air/</link>
		<comments>http://marine-ac.com/marine-ac-cruisair-marine-air/#comments</comments>
		<pubDate>Fri, 15 Jul 2011 16:03:12 +0000</pubDate>
		<dc:creator>Steve Pooler</dc:creator>
				<category><![CDATA[Marine AC]]></category>
		<category><![CDATA[Boat A/C]]></category>
		<category><![CDATA[Boat A/C forum]]></category>
		<category><![CDATA[boat ac troubleshooting]]></category>
		<category><![CDATA[Marine A/C forum]]></category>

		<guid isPermaLink="false">http://marine-ac.com/?p=2166</guid>
		<description><![CDATA[50 or so years ago&#8230;Marine A/C was custom installed only (no production units)&#8230;This was what was installed in yachts for A/C&#8230;The system is what we call &#8220;Modulating&#8221; with a Semi Hermetic compressor, and each cabin had it&#8217;s own thermostat that shut the flow of refrigerant off to that cabin when it reached the selected temp. [...]]]></description>
			<content:encoded><![CDATA[<p><a href="http://marine-ac.com/wp-content/uploads/2011/07/158b3eu.jpg"><img class="aligncenter size-full wp-image-2513" title="50 Year Old Custom Marine Air Conditioning" src="http://marine-ac.com/wp-content/uploads/2011/07/158b3eu.jpg" alt="" width="640" height="480" /></a>50 or so years ago&#8230;Marine A/C was custom installed only (no production units)&#8230;This was what was installed in yachts for A/C&#8230;The system is what we call &#8220;Modulating&#8221; with a Semi Hermetic compressor, and each cabin had it&#8217;s own thermostat that shut the flow of refrigerant off to that cabin when it reached the selected temp.</p>
<p>One compressor &amp; 5 air handlers in this case&#8230;This system is in a Berger Yacht &amp; cools the lower deck cabins&#8230;</p>
<p>The Cruisair units in the second picture were added after the Pilot House/Aft Deck were enclosed&#8230;</p>
<p>Sorry for the not so good pictures but my iPhone has no flash (waiting for upgrade time)</p>
<p>&nbsp;</p>
<p>Steve~</p>
<p>&nbsp;</p>
]]></content:encoded>
			<wfw:commentRss>http://marine-ac.com/marine-ac-cruisair-marine-air/feed/</wfw:commentRss>
		<slash:comments>0</slash:comments>
		</item>
		<item>
		<title>Marine AC Compressor SmartStart, Soft Start, Hard Start Assist</title>
		<link>http://marine-ac.com/marine-ac-compressor-smartstart-soft-start-hard-start-assist-2/</link>
		<comments>http://marine-ac.com/marine-ac-compressor-smartstart-soft-start-hard-start-assist-2/#comments</comments>
		<pubDate>Mon, 08 Nov 2010 15:36:14 +0000</pubDate>
		<dc:creator>Steve Pooler</dc:creator>
				<category><![CDATA[Cruisair Store]]></category>
		<category><![CDATA[Marine A/C Store]]></category>
		<category><![CDATA[Marine Airrrr Store]]></category>
		<category><![CDATA[boat ac troubleshooting]]></category>
		<category><![CDATA[Chilled Water]]></category>
		<category><![CDATA[Compressor Starting]]></category>
		<category><![CDATA[Cruisair]]></category>
		<category><![CDATA[Dometic]]></category>
		<category><![CDATA[Hard Start Compressor]]></category>
		<category><![CDATA[marine ac troubleshooting]]></category>
		<category><![CDATA[Marine Air]]></category>

		<guid isPermaLink="false">http://marine-ac.com/?p=2166</guid>
		<description><![CDATA[Got a Compressor that is a bit hard starting&#8230;Maybe marginal Shore Power or Generator causing Tripped Breakers, Lights Dimming, or Battery Backups beeping every time the A/C starts&#8230;This could be your answer&#8230; I have installed several and found the claims to be true&#8230; The instructions are pretty straight forward, but I can also provide an [...]]]></description>
			<content:encoded><![CDATA[<p><strong>Got a Compressor that is a bit hard starting&#8230;Maybe marginal Shore Power or Generator causing Tripped Breakers, Lights Dimming, or Battery Backups beeping every time the A/C starts&#8230;This could be your answer&#8230;</strong></p>
<p><strong><a href="http://marine-ac.com/wp-content/uploads/2010/11/SmartStart_no_wires_face_right1.jpg"><img class="aligncenter size-medium wp-image-1038" title="SmartStart_no_wires_face_right" src="http://marine-ac.com/wp-content/uploads/2010/11/SmartStart_no_wires_face_right1-300x225.jpg" alt="" width="300" height="225" /></a></strong></p>
<p><strong><a href="http://marine-ac.com/wp-content/uploads/2010/11/SmartStart_Compare_Bar_Graph1.jpg"><img class="aligncenter size-medium wp-image-1039" title="SmartStart_Compare_Bar_Graph" src="http://marine-ac.com/wp-content/uploads/2010/11/SmartStart_Compare_Bar_Graph1-300x214.jpg" alt="" width="300" height="214" /></a></strong></p>
<p style="text-align: center;"><a style="margin: 12px auto 6px auto; font-family: Helvetica,Arial,Sans-serif; font-style: normal; font-variant: normal; font-weight: normal; font-size: 14px; line-height: normal; font-size-adjust: none; font-stretch: normal; display: block; text-decoration: underline;" title="View Smart Start by Dometic on Scribd" href="http://www.scribd.com/doc/41570302/Smart-Start-by-Dometic">
<object width="625" height="444">
<param name="allowfullscreen" value="true" />
<param name="allowscriptaccess" value="always" />
<param name="movie" value="http://www.youtube.com/v/iEu5clbUbts&autoplay=0&loop=0&rel=0" />
<param name="wmode" value="transparent">
<embed src="http://www.youtube.com/v/iEu5clbUbts&autoplay=0&loop=0&rel=0" type="application/x-shockwave-flash" wmode="transparent" allowfullscreen="true" allowscriptaccess="always" width="625" height="444">
</embed>
</object>

<br /></a></p>
<p><object id="doc_74812" style="outline: medium none;" width="100%" height="600" classid="clsid:d27cdb6e-ae6d-11cf-96b8-444553540000" codebase="http://download.macromedia.com/pub/shockwave/cabs/flash/swflash.cab#version=6,0,40,0"><param name="data" value="http://d1.scribdassets.com/ScribdViewer.swf" /><param name="wmode" value="opaque" /><param name="allowFullScreen" value="true" /><param name="allowScriptAccess" value="always" /><param name="FlashVars" value="document_id=41570302&amp;access_key=key-2nf4fz1w1feesjymqz16&amp;page=1&amp;viewMode=book" /><param name="src" value="http://d1.scribdassets.com/ScribdViewer.swf" /><param name="allowfullscreen" value="true" /><param name="flashvars" value="document_id=41570302&amp;access_key=key-2nf4fz1w1feesjymqz16&amp;page=1&amp;viewMode=book" /><param name="allowscriptaccess" value="always" /><embed id="doc_74812" style="outline: medium none;" width="100%" height="600" type="application/x-shockwave-flash" src="http://d1.scribdassets.com/ScribdViewer.swf" data="http://d1.scribdassets.com/ScribdViewer.swf" wmode="opaque" allowFullScreen="true" allowScriptAccess="always" FlashVars="document_id=41570302&amp;access_key=key-2nf4fz1w1feesjymqz16&amp;page=1&amp;viewMode=book" allowfullscreen="true" flashvars="document_id=41570302&amp;access_key=key-2nf4fz1w1feesjymqz16&amp;page=1&amp;viewMode=book" allowscriptaccess="always" /></object></p>
<p><strong>I have installed several and found the claims to be true&#8230;</strong></p>
<p><strong>The instructions are pretty straight forward, but I can also provide an installation video&#8230;</strong></p>
<p><strong>Steve~</strong></p>
<p><strong><br /></strong></p>
<p style="text-align: center;">
<object width="625" height="444">
<param name="allowfullscreen" value="true" />
<param name="allowscriptaccess" value="always" />
<param name="movie" value="http://www.youtube.com/v/LVZ3Dgb_QAI&autoplay=0&loop=0&rel=0" />
<param name="wmode" value="transparent">
<embed src="http://www.youtube.com/v/LVZ3Dgb_QAI&autoplay=0&loop=0&rel=0" type="application/x-shockwave-flash" wmode="transparent" allowfullscreen="true" allowscriptaccess="always" width="625" height="444">
</embed>
</object>

<strong><br /></strong></p>
]]></content:encoded>
			<wfw:commentRss>http://marine-ac.com/marine-ac-compressor-smartstart-soft-start-hard-start-assist-2/feed/</wfw:commentRss>
		<slash:comments>0</slash:comments>
		</item>
		<item>
		<title>Marine Air Conditioning System Maintenance</title>
		<link>http://marine-ac.com/marine-air-conditioning-system-maintenance/</link>
		<comments>http://marine-ac.com/marine-air-conditioning-system-maintenance/#comments</comments>
		<pubDate>Sat, 06 Nov 2010 00:54:55 +0000</pubDate>
		<dc:creator>Steve Pooler</dc:creator>
				<category><![CDATA[About]]></category>
		<category><![CDATA[AC/Systems]]></category>
		<category><![CDATA[Cruisair]]></category>
		<category><![CDATA[Maintence Tips]]></category>
		<category><![CDATA[Marine AC]]></category>
		<category><![CDATA[Marine Air]]></category>
		<category><![CDATA[boat ac troubleshooting]]></category>
		<category><![CDATA[Fault Code]]></category>
		<category><![CDATA[HHH]]></category>
		<category><![CDATA[HI P5]]></category>
		<category><![CDATA[HI PS]]></category>
		<category><![CDATA[High Head Pressure]]></category>
		<category><![CDATA[LO P5]]></category>
		<category><![CDATA[Marine A/C maintenance]]></category>
		<category><![CDATA[marine ac troubleshooting]]></category>
		<category><![CDATA[Strainer]]></category>
		<category><![CDATA[Yacht A/C]]></category>

		<guid isPermaLink="false">http://marine-ac.com/?p=2166</guid>
		<description><![CDATA[Without water flow....You have NO cooling !
Service people on the docks (at least the better ones) can walk down the dock during the summer and tell which boats they are likely to be getting a call from next just by the flow of water (or lack of) going overboard on each boat....Lack of seawater flow can cause other problems besides loss of cooling...

]]></description>
			<content:encoded><![CDATA[<p><a href="http://marine-ac.com/wp-content/uploads/2008/11/img_0048.jpg"><img class="alignright size-medium wp-image-47" title="Marine AC" src="http://marine-ac.com/wp-content/uploads/2008/11/img_0048-300x225.jpg" alt="" width="300" height="225" /></a><br /> Greetings All,</p>
<p><strong>Let&#8217;s start with the basics&#8230;</strong></p>
<p>Seawater flow thru your A/C system is primary&#8230;</p>
<h3>Without water flow&#8230;.You have NO cooling !</h3>
<p>Service people on the docks (at least the better ones) can walk down the dock during the summer and tell which boats they are likely to be getting a call from next just by the flow of water (or lack of) going overboard on each boat&#8230;.Lack of seawater flow can cause other problems besides loss of cooling&#8230;</p>
<ul>
<li>Lack of seawater flow causes high system operating pressures</li>
<li>This, in turn increases the amperage draw from the A/C unit</li>
<li>Possibly leading to: Burnt up wiring at switches or shore cord ends</li>
</ul>
<p>Many of these symptoms can stem back to the cause of low water flow. If the flow is allowed to remain restricted,  compressor failure can also occur in some older systems.</p>
<p>Different than land based systems, Marine systems installed below decks have no fan to remove the heat from the refrigerant&#8230;They use water to carry away the heat for many reasons&#8230;<span id="more-35"></span></p>
<ul>
<li>Water is more efficient than air as a heat exchange medium</li>
<li>Size of a unit with air cooling is much larger, thus making air cooling impractical on boats</li>
<li>Air cooled units require a exit path for the heat so that the space they are in does not continue to heat up as they run, thus reducing their efficiency further</li>
</ul>
<p><a href="http://marine-ac.com/wp-content/uploads/2008/11/07-19-07_1340.jpg"><img class="size-medium wp-image-37 aligncenter" title="Clogged Seawater Strainer" src="http://marine-ac.com/wp-content/uploads/2008/11/07-19-07_1340-300x225.jpg" alt="" width="300" height="225" /></a></p>
<p>As you see from the picture above&#8230;.It&#8217;s an example of a seawater strainer to a system that has seen little love, and this system of course did not cool.</p>
<p>Every boat owner should become familiar with their boats overboard flow rate when the system is clean, and become accustomed to glancing at it every chance they get&#8230;Once you have established what is normal for your boat, a simple glance may be enough to recognize a mounting problem, and thus head off a ruined trip due to the loss of A/C&#8230;</p>
<p>The first question a tech may/should ask when he gets a call Is&#8230;&#8221;How is the seawater flow ?&#8221;</p>
<p>More frequently than not&#8230;The owners answer is he thinks it ok, or Yes it&#8217;s flowing&#8230;Only for us to arrive to find not much more than a trickle&#8230;.All this is ok for us as techs&#8230;but if you would like to save that expensive service call&#8230;Keeping your strainer from looking like the picture is a great start !</p>
<p>Seawater strainer maintenance is not hard to do&#8230;But of course every boat or installation is different. You should also know that the more the system/s run&#8230;The more frequently you will need to clean the strainer. During the winter months here in central Florida we find that due to cooler water (marine organisms seem to grow more slowly in cooler water) and obviously less usage you may not need to clean the strainer but once a month&#8230;.Summer is a different story !</p>
<p>Depending on where your boat is moored, Tidal flow, Water Temp, and Running the system/s 24/7 can require cleaning the strainer as often as every week&#8230;I have even seen worst case situations where a boat may be moored in a pass with much tidal flow (and grass flats nearby) causing the grass to &#8220;Tumble&#8221; in the water down to where the thru hull is located, thus requiring the strainer basket to be emptied in a matter of hours&#8230;</p>
<p>Steve~</p>
]]></content:encoded>
			<wfw:commentRss>http://marine-ac.com/marine-air-conditioning-system-maintenance/feed/</wfw:commentRss>
		<slash:comments>9</slash:comments>
		</item>
		<item>
		<title>A/C System Ices Up</title>
		<link>http://marine-ac.com/ac-system-ices-up/</link>
		<comments>http://marine-ac.com/ac-system-ices-up/#comments</comments>
		<pubDate>Fri, 16 Jul 2010 17:21:36 +0000</pubDate>
		<dc:creator>Steve Pooler</dc:creator>
				<category><![CDATA[AC/Systems]]></category>
		<category><![CDATA[Featured-Home]]></category>
		<category><![CDATA[Maintence Tips]]></category>
		<category><![CDATA[ac iceing]]></category>
		<category><![CDATA[Boat A/C]]></category>
		<category><![CDATA[boat ac troubleshooting]]></category>
		<category><![CDATA[Fault Code]]></category>
		<category><![CDATA[Fix my A/C]]></category>
		<category><![CDATA[HHH]]></category>
		<category><![CDATA[HI P5]]></category>
		<category><![CDATA[HI PS]]></category>
		<category><![CDATA[High Head Pressure]]></category>
		<category><![CDATA[LO P5]]></category>
		<category><![CDATA[LO PS]]></category>
		<category><![CDATA[LPF]]></category>
		<category><![CDATA[Marine A/C maintenance]]></category>
		<category><![CDATA[marine ac troubleshooting]]></category>
		<category><![CDATA[Yacht A/C]]></category>
		<category><![CDATA[yacht ac troubleshooting]]></category>

		<guid isPermaLink="false">http://marine-ac.com/?p=2166</guid>
		<description><![CDATA[I notice from the Google searches&#8230;That A/C System Icing is a search done often.. Though there can be many reasons for system icing&#8230;There are a few that the DIY boater can rule out before calling the service guy ( I can discuss other reasons in the forum but here are a few of the basic answers) Direct Expansion [...]]]></description>
			<content:encoded><![CDATA[<p>I notice from the Google searches&#8230;That A/C System Icing is a search done often..<div id="attachment_1790" class="wp-caption alignright" style="width: 310px"><a href="http://marine-ac.com/"><img class="size-medium wp-image-1790" title="IceBoatB" src="http://marine-ac.com/wp-content/uploads/2010/07/IceBoatB-300x246.jpg" alt="Ac System Icing" width="300" height="246" /></a><p class="wp-caption-text">Not &quot;Good&quot; Ice</p></div></p>
<p>Though there can be many reasons for system icing&#8230;There are a few that the DIY boater can rule out before calling the service guy ( I can discuss other reasons in the forum but here are a few of the basic answers)</p>
<ul>
<li>Direct Expansion A/C (as opposed to Chilled Water) systems rely heavily on Air Flow across the evaporator coil in order to pick up the designed amount of heat the system was engineered to remove (BTU) and any loss of that designed air flow can cause the system to Ice.</li>
</ul>
<p><span id="more-243"></span></p>
<p>Regardless of freon charge (explained later) the system must first and foremost have the correct amount of air flow&#8230;So air flow should be the first thing to check&#8230;Below are some reasons for reduced air flow&#8230;</p>
<ul>
<li>Dirty or clogged Return Air Filters&#8230;Some systems may have two filters installed&#8230;One at the Return grill, and a second that shipped with the unit on the evaporator fins ( folks tend to forget this one, or never knew it was there in the first place)</li>
<li>Dirty or clogged evaporator coil/s due to not cleaning, or No/Poor return air filters installed.</li>
<li>Fan Speed Adjusted Too Low (Sometimes done to attain a quiet blower)</li>
<li>Undersized Return or Supply Ducting for the BTU System installed&#8230;This was the installers responsibility to size correctly, but all too often there is not sufficient space for where they want to run to size it properly&#8230;Thus a problem for the systems life, which is most always shortened dramatically from this practice&#8230;They should find another way, or reduce the size of the system to match the installation&#8230;Blowers can only move rated flow thru the proper sized duct.</li>
</ul>
<p>Another reason which sometimes is overlooked&#8230;</p>
<ul>
<li>Very Cold Cabin&#8230;The colder the cabin&#8230;The less heat there is to pick up&#8230;Thus more Air Flow is needed to increase the amount of heat (that&#8217;s now not there) being picked up&#8230;A/C systems are called &#8220;High Temp&#8221; systems&#8230;they are designed to do exactly as the name implies&#8230;Air Condition&#8230;Not Refrigerate&#8230;That&#8217;s what Refrigerators &amp; Freezers are designed to do&#8230;Your A/C system is not designed to cool much below 68 degrees F&#8230;Though it will try to do so if you ask it&#8230;</li>
<li>Most of the newer Digital Cabin Controls have algorithms to &#8220;help&#8221; with this by shutting off the compressor for short periods until the desired room setpoint is attained, but they are not defrost cycles with coil heaters like you might find in a system designed to run at lower temps.</li>
</ul>
<p>Last but Not least is&#8230;</p>
<ul>
<li>Low Refrigerant Charge causes Icing&#8230;You Ask Huh ???&#8230;Why would low freon cause it to ice ?&#8230;I thought the more freon the colder&#8230;Not So with refrigerants&#8230;I&#8217;ll try to explain briefly&#8230;</li>
</ul>
<p>Pressure &amp; Temperature Automatically Correspond with Refrigerants&#8230;The Lower the Pressure&#8230;The Lower the Temperature of the refrigerant ( and Vise Verse) Regardless of how much is in there&#8230;I&#8217;ll leave it at that for now but can explain further in another article, or in the forum if requested.</p>
<ul>
<li>The question here is&#8230;Why is the system low on freon ???</li>
</ul>
<p>These systems are sealed, and should not require seasonal charging, like automotive systems that tend to leak because they have rubber hoses, o-rings &amp; compressor shaft seals&#8230;These systems are all copper tubing, with soldered &amp; mechanical flare joints.</p>
<ul>
<li>Did someone let out freon because the unit was running high pressure ? (usually an indication of  loss of seawater flow, or a dirty condenser)</li>
<li>Has the system started leaking due to a poor connection (Flare or otherwise) or maybe electrolysis eating away at solder joints ?</li>
</ul>
<p>If So&#8230;Then the leak needs to be located &amp; repaired to save burning up the compressor&#8230;The compressor is the heart of the system, it&#8217;s expensive, and relies on the proper amount of refrigerant return to stay cool&#8230;It will run Very Hot without enough Freon return regardless of seawater flow&#8230;and even if the system (air handler or tubing) is icing&#8230;The compressor will run hot from that lack of freon.</p>
<p>Hope this helps answer a few questions, but if not&#8230;Or if it creates more&#8230;Drop me a line (preferably in the forum so that others can benefit as well)  Always glad to answer.</p>
<p>Steve~</p>
]]></content:encoded>
			<wfw:commentRss>http://marine-ac.com/ac-system-ices-up/feed/</wfw:commentRss>
		<slash:comments>0</slash:comments>
		</item>
		<item>
		<title>Free Marine A/C &amp; Refrigeration Troubleshooting</title>
		<link>http://marine-ac.com/free-marine-ac-refrigeration-troubleshooting/</link>
		<comments>http://marine-ac.com/free-marine-ac-refrigeration-troubleshooting/#comments</comments>
		<pubDate>Wed, 24 Mar 2010 14:47:01 +0000</pubDate>
		<dc:creator>Steve Pooler</dc:creator>
				<category><![CDATA[DIY Questions]]></category>
		<category><![CDATA[ac iceing]]></category>
		<category><![CDATA[Boat A/C]]></category>
		<category><![CDATA[Boat A/C forum]]></category>
		<category><![CDATA[boat ac troubleshooting]]></category>
		<category><![CDATA[Boat Air Conditioning]]></category>
		<category><![CDATA[Chilled Water]]></category>
		<category><![CDATA[Cold Plate/Holding Plate]]></category>
		<category><![CDATA[Cruisair]]></category>
		<category><![CDATA[Digital Marine A/C Controls]]></category>
		<category><![CDATA[Dometic]]></category>
		<category><![CDATA[Eutectic]]></category>
		<category><![CDATA[Eutectic Refrigeration]]></category>
		<category><![CDATA[Fix my A/C]]></category>
		<category><![CDATA[Free Marine AC Troubleshooting Help]]></category>
		<category><![CDATA[High Head Pressure]]></category>
		<category><![CDATA[Marine A/C Controls]]></category>
		<category><![CDATA[Marine A/C forum]]></category>
		<category><![CDATA[Marine A/C maintenance]]></category>
		<category><![CDATA[PR3X]]></category>
		<category><![CDATA[PR8X]]></category>
		<category><![CDATA[Pump Relays]]></category>
		<category><![CDATA[Strainer]]></category>
		<category><![CDATA[Yacht A/C]]></category>
		<category><![CDATA[yacht ac troubleshooting]]></category>
		<category><![CDATA[Yacht Air Conditioning]]></category>

		<guid isPermaLink="false">http://marine-ac.com/?p=2166</guid>
		<description><![CDATA[Greetings All&#8230; This is just a note to confirm that I offer FREE Troubleshooting help for your Marine A/C &#38; Refrigeration issues&#8230;But I ONLY do this in the FORUM section&#8230;If you can&#8217;t take the time to register &#38; ask in the FORUM&#8230;I usually won&#8217;t respond&#8230;(this section is not setup for dialog/discussion&#8230;it&#8217;s only setup for comments) My only request [...]]]></description>
			<content:encoded><![CDATA[<p>Greetings All&#8230;</p>
<p><a href="http://marine-ac.com/wp-content/uploads/2010/03/free-sign.gif"><img class="alignright size-full wp-image-1819" title="free-sign" src="http://marine-ac.com/wp-content/uploads/2010/03/free-sign.gif" alt="" width="388" height="309" /></a></p>
<p>This is just a note to confirm that I offer FREE Troubleshooting help for your Marine A/C &amp; Refrigeration issues&#8230;But I ONLY do this in the FORUM section&#8230;If you can&#8217;t take the time to register &amp; ask in the FORUM&#8230;I usually won&#8217;t respond&#8230;(this section is not setup for dialog/discussion&#8230;it&#8217;s only setup for comments)</p>
<p>My only request in return is that you Consider me when buying replacement parts, or units&#8230;And that if local, you also consider my services&#8230;.But how&#8217;s they saying go ?</p>
<p>No Purchase Necessary&#8230;That price can&#8217;t be beat at half the cost !!!</p>
<p>All you need to do is join &amp; ask in the FORUM section most relative to your issue  <a href="http://marine-ac.com/forum/">http://marine-ac.com/forum/</a></p>
<p>Post your own title (thread) in the section that applies, and I&#8217;ll be happy to respond with my best honest advise&#8230;</p>
<p>Thanks Again,</p>
<p>Steve~</p>
]]></content:encoded>
			<wfw:commentRss>http://marine-ac.com/free-marine-ac-refrigeration-troubleshooting/feed/</wfw:commentRss>
		<slash:comments>6</slash:comments>
		</item>
		<item>
		<title>Marine A/C &amp; New Refrigerant Regulations</title>
		<link>http://marine-ac.com/marine-ac-new-refrigerant-regulations/</link>
		<comments>http://marine-ac.com/marine-ac-new-refrigerant-regulations/#comments</comments>
		<pubDate>Wed, 27 Jan 2010 16:16:00 +0000</pubDate>
		<dc:creator>Steve Pooler</dc:creator>
				<category><![CDATA[About]]></category>
		<category><![CDATA[AC/Systems]]></category>
		<category><![CDATA[Cruisair]]></category>
		<category><![CDATA[Maintence Tips]]></category>
		<category><![CDATA[Marine AC]]></category>
		<category><![CDATA[Marine Air]]></category>
		<category><![CDATA[ac iceing]]></category>
		<category><![CDATA[Boat A/C]]></category>
		<category><![CDATA[Boat A/C forum]]></category>
		<category><![CDATA[boat ac troubleshooting]]></category>
		<category><![CDATA[Boat Air Conditioning]]></category>
		<category><![CDATA[Dometic]]></category>
		<category><![CDATA[Fix my A/C]]></category>
		<category><![CDATA[High Head Pressure]]></category>
		<category><![CDATA[Marine A/C maintenance]]></category>
		<category><![CDATA[marine ac iceing]]></category>
		<category><![CDATA[marine ac troubleshooting]]></category>
		<category><![CDATA[Yacht A/C]]></category>
		<category><![CDATA[yacht ac troubleshooting]]></category>
		<category><![CDATA[Yacht Air Conditioning]]></category>

		<guid isPermaLink="false">http://marine-ac.com/?p=2166</guid>
		<description><![CDATA[Due to new 2010 EPA regulations regarding the phase out of our long used R-22 A/C refrigerant systems...

Here's what I can share at this point from the Cruisair/Marine Air perspective &#038; what I have been told.]]></description>
			<content:encoded><![CDATA[<p><img class="alignleft size-full wp-image-2528" style="margin-left: 0px; margin-right: 10px;" title="epa-" src="http://marine-ac.com/wp-content/uploads/2010/01/epa-.jpg" alt="" width="225" height="225" />Due to new 2010 EPA regulations regarding the phase out of our long used R-22 A/C refrigerant systems&#8230;</p>
<p>Here&#8217;s what I can share at this point from the Cruisair/Marine Air perspective &amp; what I have been told.</p>
<p><span id="more-401"></span></p>
<p>Self Contained R-22 units are no longer in production&#8230;sort of&#8230;</p>
<p>Since 417a is a drop in replacement for R-22 you can get the R-22 units (but they are shipping charged with R-417a)</p>
<p>We are told that the R-417a drop in replacement refrigerant for R-22 is 17% less efficient than the R-22 in the same unit (like running 60Hz equipment on 50Hz power)</p>
<p>So if you bought a new R-417a unit&#8230;You can evacuate the R-417a and re-charge that unit with R-22 to realize the same performance as a R-22 unit that was purchased before the production change&#8230;</p>
<p>You can also evacuate a older R-22 system &amp; recharge with 417a&#8230;But the 17% performance drop still applies&#8230;</p>
<p>R-22 refrigerant should still be available for quite some time yet&#8230;But&#8230;The price will climb pretty quickly.</p>
<p><span style="color: #0000ff;">Edit:  5/1/2011&#8230;2020 is slated to be the end of production of R-22 in the US&#8230;None will be imported either&#8230;But at that point, if you still have an operational R-22 system, it can be evacuated and re-charged with R-417a.</span></p>
<p>The new R-410a cannot be used in a R-22/R417a system even with evacuation&#8230;It&#8217;s not compatible with the oil in the 22 system &amp; the pressures will run too high in that system (metering devise is not set for it either)</p>
<p>My distributor has about 3 months worth of sales of units with R-22 available, but after they are gone he will only stock the new R-410a units&#8230;.And is now only ordering Self Contained unit with the new R410a.</p>
<p><span style="color: #0000ff;">5/11/2011&#8230;R-22/R417 self contained units are no longer in stock.</span></p>
<p>Split or Remote systems are a whole different story&#8230;</p>
<p>One thing they are the same in is that none of the existing systems can run the new R-410a, but they can run the R-417a with the 17% drop in performance&#8230;.but the problem is bigger with small split systems.</p>
<p>Typically the 16K &amp; smaller split systems have always used piston type compressors as opposed to the rotary type that have been used in self contained units for many years now&#8230;</p>
<p>The reason for this is that the rotary type compressor does not lend itself well to long copper line runs&#8230;<br /> Rotary crankcases don&#8217;t hold enough oil for the migration of oil with the refrigerant throughout the longer line runs in split systems&#8230;<br /> It&#8217;s my understanding that the rotary can run out of oil before it has a chance to return with the refrigerant, and thus can ruin itself in a split system from lack of lubrication.</p>
<p>The compressor manufacturers are being forced to phase out production of the lower efficiency piston compressors by the EPA or whomever&#8230;</p>
<p><span style="color: #0000ff;">5/1/2011&#8230;We still have no info on when this might happen but as of this date&#8230;Replacement R-22 split system units with the older piston compressors are still in production&#8230;But only ship with R-417a which can be evacuated after installation &amp; replaced with R-22 to maintain efficiency.</span></p>
<p>Scroll compressors would be a great alternative, but as of yet&#8230;The compressor manufacturers have not developed Scroll compressors in the smaller sizes that are required for our smaller Marine split systems (the larger than 16k marine units are using scrolls now)<br /> I guess they figure the Marine market is too small to develop new small scrolls for, and that the rotary&#8217;s are fine for the home window unit market (which is what the the rotary&#8217;s were developed for)</p>
<p>I know that Dometic Cruisair/Marine Air has been testing small splits using rotary&#8217;s for quite some time now&#8230;So far they aren&#8217;t saying much&#8230;</p>
<p>Until then&#8230;They are only offering the same piston type smaller split systems and shipping with R-417a (the drop in replacement for R-22) to meet the new regulations&#8230;.The Larger splits (over 16K) will be available as either R-417a (mainly for replacements of the older R-22 units) or the new R-410a units, but to utilize R-410a condensing unit you must also change the air handler&#8230;No need for new copper tubing runs.</p>
<p><span style="color: #0000ff;">Dometic is now offering their new &#8220;Emerald Series&#8221; split/remote systems with rotary compressors (16K &amp; below) Also with  TXV&#8217;s (thermostatic expansion valve) metering devises at both the condensing unit &amp; air handler (2 TXV&#8217;s)&#8230;Larger than 16K &#8220;Emerald Series&#8221; systems are Scroll compressors.</span></p>
<p>Steve~</p>
]]></content:encoded>
			<wfw:commentRss>http://marine-ac.com/marine-ac-new-refrigerant-regulations/feed/</wfw:commentRss>
		<slash:comments>0</slash:comments>
		</item>
		<item>
		<title>Marine A/C Icing in Heat</title>
		<link>http://marine-ac.com/marine-ac-icing-in-heat/</link>
		<comments>http://marine-ac.com/marine-ac-icing-in-heat/#comments</comments>
		<pubDate>Sat, 23 Jan 2010 17:10:47 +0000</pubDate>
		<dc:creator>Steve Pooler</dc:creator>
				<category><![CDATA[DIY Questions]]></category>
		<category><![CDATA[Icing Up]]></category>
		<category><![CDATA[ac iceing]]></category>
		<category><![CDATA[Boat A/C]]></category>
		<category><![CDATA[boat ac troubleshooting]]></category>
		<category><![CDATA[Boat Air Conditioning]]></category>
		<category><![CDATA[Fix my A/C]]></category>
		<category><![CDATA[Marine AC]]></category>
		<category><![CDATA[marine ac iceing]]></category>
		<category><![CDATA[marine ac pumps]]></category>
		<category><![CDATA[marine ac troubleshooting]]></category>
		<category><![CDATA[yacht ac troubleshooting]]></category>
		<category><![CDATA[Yacht Air Conditioning]]></category>

		<guid isPermaLink="false">http://marine-ac.com/?p=2166</guid>
		<description><![CDATA[I have been experiencing an a/c problem also but on the heat mode side. I have 4 A/C system with one giving me a icing problem on the compressor unit. Starting on the suction side and loop tubing of the remote unit is freezing up with heavy ice. The compressor is hot to touch. Check air handling unit… High fan, clean filter giving out warm air. Water flow thru compressor unit and 3 other unit's has a high flow rate. Water temp is around low 50's.]]></description>
			<content:encoded><![CDATA[<p><img class="alignleft size-medium wp-image-2532" style="margin-left: 0px; margin-right: 10px;" title="iced-boat" src="http://marine-ac.com/wp-content/uploads/2010/01/iced-boat-245x300.jpg" alt="" width="196" height="240" />It&#8217;s the time of year that we all need heat…Even here in Florida this year…Global Warming My…?</p>
<p>Anyway…</p>
<p>Below is a post I answered in the Hatteras Owners Forum, and it seems to be a subject that many of you all are searching for answers to this time of year…It also applies to cooling in the summer, but is mostly about system Icing &amp; the causes…I&#8217;m also going to  link this article to a Forum post here on this site so that anyone that may have questions or need further clarifications may ask away there…</p>
<div>
<div>
<div>Quote:</div>
<table style="width: 100%;" border="0" cellspacing="0" cellpadding="6">
<tbody>
<tr>
<td>
<div>Originally Posted by <strong>SeaWhisper</strong> <a href="/forum/troubleshooting/marine-ac-icing-in-heat/showthread.php?p=152008#post152008" rel="nofollow" target="_blank"><img src="/forum/troubleshooting/marine-ac-icing-in-heat/images/bluesaint/buttons/viewpost.gif" alt="View Post" border="0" /></a></div>
<div>Don&#8217;t mean to jump on this thread ! Steve if your following, I have been experiencing an a/c problem also but on the heat mode side. I have 4 A/C system with one giving me a icing problem on the compressor unit. Starting on the suction side and loop tubing of the remote unit is freezing up with heavy ice. The compressor is hot to touch. Check air handling unit… High fan, clean filter giving out warm air. Water flow thru compressor unit and 3 other unit&#8217;s has a high flow rate. Water temp is around low 50&#8242;s. I can switch the unit to cool mode and it will melt the ice of the compressor unit… Your thoughts on what may be causes the heavy icing…. Low freon? Unit is a 16,000 btu maybe 2 years old, with smxir controls. Thanks…</div>
</td>
</tr>
</tbody>
</table>
</div>
<p><span id="more-398"></span></p>
<p>Mike~</p>
<p>First I need to clarify what you mean by…&#8221;Starting on the suction side and loop tubing of the remote unit is freezing up with heavy ice. &#8220;</p>
<p>Do you mean the water coil ?</p>
<p>If so…Then it would be hard to know that the unit in question is actually getting proper water flow by looking over the side…Since all the 53 MY&#8217;s I can remember, had a single overboard discharge fitting with a 4 unit manifold attached.</p>
<p>You would need to remove the hose for the unit in question from that overboard manifold, and either let it run into the bilge or a bucket…It&#8217;s not uncommon to have a blockage or some kind of growth restricting one unit&#8217;s seawater flow….This can cause what you describe.</p>
<p>Yes the compressor will run a bit hotter in the heat mode…</p>
<p>Icing is always an indication of Low Pressure…What is causing that low pressure is key to solving it…Duh ?</p>
<p>First…Pressure &amp; Temp correspond with refrigerants…The lower the pressure of the refrigerant…The lower the temp of that refrigerant…</p>
<p>If you place a jug of refrigerant in a room and connect a pressure gauge to it…then let it get to room temp by just sitting there…</p>
<p>With a pressure temp chart for that particular refrigerant (in this case R-22) you can tell the temp of the room by the pressure shown on the pressure gauge…If that room is 32*…The gauge will read somewhere around 56-58 psi. (the chart I have with me right now jumps from 30 to 35 degrees so I&#8217;m guessing a bit but that&#8217;s close)</p>
<p>When running in heat mode the water coil is the evaporator and is on the low side of the system (cold part) the air handler is the high side (hot part)</p>
<p>In cooling they switch duties because the Reversing Valve will send the refrigerant around the system in the opposite direction.</p>
<p>Thus a &#8220;Reverse Cycle&#8221; system also known as a Heat Pump…</p>
<p>Back to what I started saying about Icing being an indication of low pressure…</p>
<p>Air Conditioning is what we call a High Temp System…Designed evaporator temps above freezing (32*)…Therefore &#8220;Low Pressure&#8221; in a R-22 A/C system is defined as below that 58-56 psi I mentioned earlier…Which will cause icing by freezing any moisture that is in contact with that surface thus blocking flow…Either Air or Water (depending on which mode you are running in)</p>
<p>A/C (and refrigeration) is all about moving or removing heat, since there is no such thing as Cold…Just the absence of Heat…Making it feel Cold…</p>
<p>In the heat mode you are picking up heat from the water with the water coil and dumping it into the cabin, using the refrigerant as the truck to carry it, and the fan in the cabin to dump it out of the truck…Cooling is just the opposite, and uses the Cabin coil to load the truck with heat, and the water to dump it out.</p>
<p>Any restriction…Ice, Air Flow, Water flow etc…Will affect how much of that heat can be picked up by a designed size coil in both the heat &amp; or cool modes.</p>
<p>This is why icing is not good with A/C…Refrigeration is another story since it usually has defrost timers &amp; heaters…A/C does not, or should not need due to the temp range it was designed to operate in…with Above 32* evaporators.</p>
<p>The biggest problem with icing the water coil in heat mode is the danger of freezing the seawater in that coil &amp; blocking flow completely…Thus causing expansion, and a rupture of that water coil…</p>
<p>This will allow the freon to leak out into the water, and the water to leak into the freon circuit, effectively ruining the complete system by pumping that seawater throughout the system with the compressor.</p>
<p>Low amount of freon causing icing ?…Yes this can also act the same as flow restriction…</p>
<p>Either way…Low freon, or Flow restriction…If the truck/s can&#8217;t get full for every circuit (restriction) or don&#8217;t start full (low freon) you are not moving the designed amount of heat that the system was made to transfer…Both of which will cause Low Pressure on the on the suspension of the trucks…</p>
<p>Back to:</p>
<p>Low pressure = Low temp = Icing…</p>
<p>Icing = Restriction = Less Flow = Lower Pressure…etc…etc…</p>
<p>One compounds another.</p>
<p>I should also add that lack of heat (or low temp) of either the water (in heating) or the cabin air (in cooling) will cause low pressure due to the fact enough heat is not there for the system to pick up in the first place&#8230;Low temp again equals low pressure, and the systems job is to move heat.</p>
<p>I know that was long guys…But I hope it helps in a lot of these questions…I know it can be confusing, or boring to read but it&#8217;s all part of understanding what is happening…</p>
<p>I tried to put it into the easiest layman&#8217;s terms I could think of…If you have any questions on what I said just ask &amp; I will try to clear them up.</p>
<p>Steve~</p>
</div>
]]></content:encoded>
			<wfw:commentRss>http://marine-ac.com/marine-ac-icing-in-heat/feed/</wfw:commentRss>
		<slash:comments>0</slash:comments>
		</item>
		<item>
		<title>AC Filters, Coils &amp; Pump Systems Maintenance &amp; Checkup</title>
		<link>http://marine-ac.com/happy-2009-to-boat-owners/</link>
		<comments>http://marine-ac.com/happy-2009-to-boat-owners/#comments</comments>
		<pubDate>Thu, 07 Jan 2010 03:56:48 +0000</pubDate>
		<dc:creator>Steve Pooler</dc:creator>
				<category><![CDATA[Air Flow]]></category>
		<category><![CDATA[Maintence Tips]]></category>
		<category><![CDATA[2PRP]]></category>
		<category><![CDATA[6PRP]]></category>
		<category><![CDATA[Boat A/C]]></category>
		<category><![CDATA[boat ac troubleshooting]]></category>
		<category><![CDATA[Cruisair]]></category>
		<category><![CDATA[Dometic]]></category>
		<category><![CDATA[Fault Code]]></category>
		<category><![CDATA[Fix my A/C]]></category>
		<category><![CDATA[HHH]]></category>
		<category><![CDATA[HI P5]]></category>
		<category><![CDATA[High Head Pressure]]></category>
		<category><![CDATA[LO P5]]></category>
		<category><![CDATA[LO PS]]></category>
		<category><![CDATA[LPF]]></category>
		<category><![CDATA[Marine A/C maintenance]]></category>
		<category><![CDATA[marine ac iceing]]></category>
		<category><![CDATA[Marine Air]]></category>
		<category><![CDATA[PR3X]]></category>
		<category><![CDATA[PR8X]]></category>
		<category><![CDATA[Pump Relays]]></category>
		<category><![CDATA[Pumps]]></category>
		<category><![CDATA[Strainer]]></category>
		<category><![CDATA[yacht ac troubleshooting]]></category>

		<guid isPermaLink="false">http://marine-ac.com/?p=2166</guid>
		<description><![CDATA[If you can get a good look at the aluminum fins…Check to see that they are not also clogged…If they are…That’s another story, and it’s probably time to call you’re A/C guy to clean them because he has access to cleaning solutions that work real well for this…and also likely has the equipment to do the job right…With less mess…]]></description>
			<content:encoded><![CDATA[<p>If it’s yourself doing the service…There are a few things you can do but since you are probably not equipped or trained as an A/C tech…There are of course some limitations…Hopefully I can point out and describe what you can do…And offer a few hints of signs of trouble without tools like gauges etc…</p>
<p><span id="more-67"></span></p>
<p><img class="alignright size-full wp-image-2535" style="border: 8px solid black;" title="dirty-condensor" src="http://marine-ac.com/wp-content/uploads/2010/01/dirty-condensor.png" alt="" width="400" height="270" />First &amp; Foremost are Filters…and not just the Sea Strainer I talked about in my last article….But the ones in the Return Air path too…</p>
<p>Direct Expansion A/C (as opposed to Chilled Water) systems rely heavily on good air flow to keep from icing up in the cool mode (Low pressure) or shutting off due to High pressure in the heating mode…</p>
<p>Generally speaking…Most boats may have two Return Air Filters per system or control…Some have more if there are more than one air handler on that system (compressor)</p>
<p>If you have a small cabin adjacent to another that the fan operates off the control in the other cabin (or just has a speed control installed in that small cabin) this may be one instance….</p>
<p>The trick to finding air handlers is to first look for the return air grill…</p>
<p>Once you have located the Return air Grill (also a likely spot for the first filter) it should be removed…Check if a filter is installed on the back side of the grill…If so remove it and set it aside…</p>
<p>Now with a flashlight…Look into that hole to see the path the air would take…At the end of that path should be the air handlers location…You may have to open another cabinet, or locker to gain access to that location, and boat builders can be very inventive in placing them in out of the way places…Ones that sometimes seem impossible to get to, but in most cases a panel can be removed for access…Here is where the second filter is located…On the aluminum fins of the evaporator coil…</p>
<p>All major manufacturers of marine A/C have shipped their units with a filter installed at the factory for some time now…If there is not one there…It has likely been removed after the system was installed…</p>
<p>I have serviced boats that the owners never knew of this factory installed filter…Or the air handler’s location for that matter…Thus when I removed the filter it looked like a piece of carpet…We all know Air does not flow thru carpet too well…</p>
<p>The manufactures install them there not knowing if a filter is going to be utilized in the grill at system installation…and If it is a clean path to the air handler (one that is not likely to get dust from another path) this filter can sometimes be discarded if it is tough to access, but it is better to have both in most cases…</p>
<p>In boats with multiple controls (more than one system) follow the above procedure till you have all the filters in hand…Take them out to the dock and have fun with the water hose…That is unless someone has installed the throw away fiberglass/paper filters, in which case I would recommend you replace them with some foam filter material that you might find at your marine A/C dealer…Or what Home Depot/Lowes etc…offers for home window A/C units.</p>
<p>Now either wait for them to dry…Or shake them out and re-install…A little water on them will not hurt a thing…</p>
<p>If you can get a good look at the aluminum fins…Check to see that they are not also clogged…If they are…That’s another story, and it’s probably time to call you’re A/C guy to clean them because he has access to cleaning solutions that work real well for this…and also likely has the equipment to do the job right…With less mess…</p>
<p>If you want to clean them yourself with a squirt bottle &amp; garden hose…He may even sell you some cleaner, or you can try Home Depot…However what they offer never seems to work as well as what he gets from the wholesale A/C supply house…</p>
<p>Before you close the cabinet back up you should also check the condition/operation of the condensate drain…Especially after washing the coil…All that stuff that got washed off is now in the condensate pan and could have clogged the drain fitting/s or hose…</p>
<p>Best way to test this is with a quart or two of tap water…You can add some bleach/Lysol/whatever to kill bacteria…But first I would run some plain water into the drain pan to find out if the drain is clogged…This way you won’t have to suck out the bleach water to avoid it dripping onto surfaces when you remove the hose to blow it out…</p>
<p>Please Note: If you have to blow out the hose or fittings, and the only way you have to do so is by mouth&#8230;Try to find a clean piece of garden hose or the like to attach to the existing fitting or hose&#8230;These hoses are where bacteria like the Legionaires Virus live&#8230;You don&#8217;t want the old hose, or the condensate water to touch or enter your mouth!!!</p>
<p>Once you are done…We are ready to start up the system/s…</p>
<p>This is a good time for you to check the seawater pump &amp; its pump relay operation (for boats with more than one A/C system supplied seawater by a single pump)</p>
<p>A seawater pump relay is a box connected to the pump that receives a signal from each separate unit…and then tells the pump to start pumping seawater when each, or any unit calls for it (starts to run)</p>
<p>They are easy to verify if they are working properly just by starting one system…Waiting for the compressor to come on…and then either looking over the side of the boat for water discharge, or if the pump actually runs by hearing it start…</p>
<p>Once you verify that that system started the pump…Switch the control off for that system…Wait for the pump to stop…Then follow the same procedure for each system by itself…You don’t want to run more than one system at a time for this test as it may be one of the other systems that brings the pump on…</p>
<p>If one of the systems does not bring the pump on…There is a problem with the pump relay box…Over the years there have been many kinds/models of pump relays, and to say how to troubleshoot each here would be kinda lengthy…However if you feel you have a problem, I will be happy to discuss your model/issue in the blog if you like…Otherwise you probably need to call Ole Faithful A/C Guy…</p>
<p>Now that we have verified Good seawater flow overboard and pump relay operation…We can run all systems…Do so for about half an hour….</p>
<p>Now we need to locate each compressor…</p>
<p>There are basically two kinds of direct expansion marine A/C systems.</p>
<ul>
<li>Self Contained units…sometimes called Stowaways or Cabin Mates…These are all in one units where the compressor, condenser, evaporator &amp; blower are all on the same base…They are usually located behind the return air grille, and under a settee or in a closet…They are more like a window unit than central A/C…As the compressor is almost in the living space and thus you can get a bit more noise…Though now days the newer rotary compressors are pretty quiet.</li>
<li>Split Systems…Sometimes called Remote…These are more like the central systems you may have at home…In that the compressor &amp; condenser are “Remotely” located and connected to the Air handler/evaporator section by copper tubing to carry the refrigerant…These systems are quieter, and have more flexibility in that they can have more than one air handler/evaporator running off one compressor…and thus allow for installation in smaller cabinets, with smaller units, to reduce air noise even more…The total of air handler BTU just must pretty closely match the condensing units capacity….</li>
</ul>
<p>Now that we have located the Compressor/s and they have run for a half hour…Be certain they are still running in cool mode…If not…Lower the temp setting of your control (t-stat)</p>
<p>Now locate the seawater condenser…It’s the tubes that horizontally (most are horizontal but some are vertical) wrap around the top of the compressor (condensing) unit…there should be at least two water hoses connected to it (some have 4) and with the palm of your hand…Grab the top coil….It should be Warm…but not Hot…</p>
<p>If it is Hot in more than one place…The unit is not performing as it should and is probably drawing more amperage than designed…</p>
<p>A couple of likely reasons…</p>
<ul>
<li>Seawater flow is not up to spec…Look for restrictions</li>
<li>Seawater condenser is dirty…Needs to be flushed with an acid solution…Similar to the radiator in your car…At any rate…Not enough heat is being removed from the refrigerant…</li>
<li>Not likely…But an overcharge of refrigerant…Maybe that last A/C guy didn’t do so good?&#8230;Or was it a buddy that said he knew what to do?</li>
<li>Even less likely…Someone replaced the seawater pump with one that doesn’t have enough GPH pumping capacity for the system…Maybe somebody’s buddy was trying to save him a buck or two…You may laugh, but I’ve seen that happen too…Hey…He meant well!</li>
<li>Most of the above reasons are probably best to call the A/C guy…Not the buddy…However you can &amp; I will walk you thru flushing a coil to remove the scale that acts like a insulating blanket preventing proper heat transfer…Just at another time…</li>
</ul>
<p>This next test is mostly for owners of Split/Remote systems…</p>
<p>Most of the newer Self Contained systems use what is called a Rotary compressor…Some of the older ones are still around that use the older reciprocating (piston) type…and to determine which you have is hard to explain if you have never seen either…But the Rotary type is usually slightly taller, and a lot skinnier than the Piston type…Have you got a Fat compressor matey?</p>
<p>Anyway…A piston type compressor that is too hot to touch on top…Is likely low on Freon…Rotary’s run Hot but Piston’s do not…</p>
<p>If either type is Cold or sweating…That’s another set of possibilities…</p>
<ul>
<li>Lack of air flow due to…Dirty filters or coils&#8230;Hey I thought we did that?</li>
<li>Overcharge of refrigerant…That buddy again?</li>
<li>Ductwork that is too small (or even crushed due to the space it was run thru) to properly handle the flow of air that the system BTU requires…We could blame…But let’s not…It won’t do any good anyway, and it’s gonna get too in depth here…Again we can discuss it in the blog for each individual circumstance…</li>
<li>Last but not least…In a split system…Multiple Air handlers that don’t add up to compressor/condensing unit BTU…We won’t go into that here either….</li>
</ul>
<p>This is getting a bit long…So in closing…I hope I have helped some…I look forward to answering any questions that I might…</p>
<p>Think of you’re A/C guy this New Years…I’m sure he thinks of you too…I know I do…</p>
<p>Steve~</p>
]]></content:encoded>
			<wfw:commentRss>http://marine-ac.com/happy-2009-to-boat-owners/feed/</wfw:commentRss>
		<slash:comments>0</slash:comments>
		</item>
		<item>
		<title>To 2010 Boat/Yacht A/C Owners</title>
		<link>http://marine-ac.com/to-2010-boatyacht-ac-owners/</link>
		<comments>http://marine-ac.com/to-2010-boatyacht-ac-owners/#comments</comments>
		<pubDate>Tue, 05 Jan 2010 16:15:59 +0000</pubDate>
		<dc:creator>Steve Pooler</dc:creator>
				<category><![CDATA[About]]></category>
		<category><![CDATA[AC/Systems]]></category>
		<category><![CDATA[Maintence Tips]]></category>
		<category><![CDATA[Marine AC]]></category>
		<category><![CDATA[Site Info]]></category>
		<category><![CDATA[Boat A/C]]></category>
		<category><![CDATA[Boat A/C forum]]></category>
		<category><![CDATA[boat ac troubleshooting]]></category>
		<category><![CDATA[Boat Air Conditioning]]></category>
		<category><![CDATA[Chilled Water]]></category>
		<category><![CDATA[Dometic]]></category>
		<category><![CDATA[Fix my A/C]]></category>
		<category><![CDATA[Florida]]></category>
		<category><![CDATA[High Head Pressure]]></category>
		<category><![CDATA[Marine A/C forum]]></category>
		<category><![CDATA[Marine A/C maintenance]]></category>
		<category><![CDATA[marine ac iceing]]></category>
		<category><![CDATA[marine ac pumps]]></category>
		<category><![CDATA[marine ac troubleshooting]]></category>
		<category><![CDATA[Marine Air]]></category>
		<category><![CDATA[Pump Relays]]></category>
		<category><![CDATA[Strainer]]></category>
		<category><![CDATA[Yacht A/C]]></category>
		<category><![CDATA[yacht ac troubleshooting]]></category>
		<category><![CDATA[Yacht Air Conditioning]]></category>

		<guid isPermaLink="false">http://marine-ac.com/?p=2166</guid>
		<description><![CDATA[Hello All&#8230;A New Year again&#8230;Hopefully yours was good&#8230;. I started this site last year to &#8220;put my feelers out&#8221;  about what owners and captains may want to learn and share about marine  a/c. The support has been more than I ever expected&#8230; So&#8230; My New Year resolution to you is expand the site we created&#8230;Because of your feedback I am [...]]]></description>
			<content:encoded><![CDATA[<p>Hello All&#8230;A New Year again&#8230;Hopefully yours was good&#8230;.</p>
<p>I started this site last year to &#8220;put my feelers out&#8221;  about what owners and captains may want to learn and share about marine  a/c.</p>
<p>The support has been more than I ever expected&#8230;</p>
<p>So&#8230; My New Year resolution to you is expand the site we created&#8230;Because of your feedback I am going to begin adding to my store to allow you to order most of the common Marine A/C system items that I found you&#8217;ve needed,  but until the store is fully operational&#8230;As always I&#8217;m here for you to contact&#8230;</p>
<p>Some important information&#8230;Sadly&#8230;Due to EPA regulations there will be no more R-22 systems/units produced in 2010&#8230;</p>
<ul>
<li>If you need to replace a R-22 condensing unit in an existing system&#8230;You will need to purchase a R-417A unit, evacuate your R-22 (which you would do anyway) and re-charge the system with R-417A (drop in replacement for R-22)&#8230;No need to change the air handler.</li>
<li>For new installations (split system or self contained) the systems have been re-designed to operate with environmentally friendly R-410A which operates at much higher pressures that the existing R-22 or R-417A systems&#8230;These R-410A units can Not be paired with the older air handlers.</li>
</ul>
<p>Your local A/C guy will know what to do &amp; have the equipment to make the change.</p>
<p>Your comments &amp; feedback are always welcome &amp; appreciated&#8230;I need things to help me write&#8230;So ask away&#8230;It does stir the thoughts&#8230;</p>
<p>Clean Sea Strainers to All, and to All a Good Year&#8230;Think of the A/C/Heat/ Refer Guy&#8230;He Does You&#8230;</p>
<p>Steve~</p>
]]></content:encoded>
			<wfw:commentRss>http://marine-ac.com/to-2010-boatyacht-ac-owners/feed/</wfw:commentRss>
		<slash:comments>0</slash:comments>
		</item>
		<item>
		<title>More on Pumps, Flow &amp; Maintence&#8230;Larger Pump ?</title>
		<link>http://marine-ac.com/more-on-pumps-flow-maintence-larger-pump/</link>
		<comments>http://marine-ac.com/more-on-pumps-flow-maintence-larger-pump/#comments</comments>
		<pubDate>Wed, 02 Sep 2009 16:10:49 +0000</pubDate>
		<dc:creator>Steve Pooler</dc:creator>
				<category><![CDATA[About]]></category>
		<category><![CDATA[AC/Systems]]></category>
		<category><![CDATA[Maintence Tips]]></category>
		<category><![CDATA[Marine AC]]></category>
		<category><![CDATA[Boat A/C]]></category>
		<category><![CDATA[Boat A/C forum]]></category>
		<category><![CDATA[boat ac troubleshooting]]></category>
		<category><![CDATA[Boat Air Conditioning]]></category>
		<category><![CDATA[Fix my A/C]]></category>
		<category><![CDATA[High Head Pressure]]></category>
		<category><![CDATA[Marine A/C maintenance]]></category>
		<category><![CDATA[marine ac pumps]]></category>
		<category><![CDATA[marine ac troubleshooting]]></category>
		<category><![CDATA[Pump Relays]]></category>
		<category><![CDATA[Pumps]]></category>
		<category><![CDATA[Yacht A/C]]></category>
		<category><![CDATA[yacht ac troubleshooting]]></category>
		<category><![CDATA[Yacht Air Conditioning]]></category>

		<guid isPermaLink="false">http://marine-ac.com/?p=2166</guid>
		<description><![CDATA[The problem with this is the water runs are now much further than when the "Central" type systems were installed all in one location close to the pump...Back then we had very little growth problems (just scale buildup in condensers that was easy to remove) and flow was much easier to plan &#038; maintain... 
]]></description>
			<content:encoded><![CDATA[<p>Below is another copy of a  post I made in the Meridian Owners Forum&#8230;If you want the full jest&#8230;<a href="http://www.meridianyachtowners.com/forum/forums/thread-view.asp?tid=1957&amp;posts=15#M18424">http://www.meridianyachtowners.com/forum/forums/thread-view.asp?tid=1957&amp;posts=15#M18424</a></p>
<blockquote>
<p>Hi Mark&#8230;Don&#8217;t know if you are still watching this thread, or if you have seen my thread over in the &#8220;Introduce Yourself&#8221; forum but here&#8217;s my take&#8230;</p>
<p>It seems that when the system was flushed, that it was flushed just well enough to break loose some stuff&#8230;Now it is floating around in the hoses and randomly blocking flow where it now lodges from time to time&#8230;<br /> Once the pump shuts off the water drains back, and with it the loose stuff moves&#8230;Only to lodge again maybe somewhere else when the pump starts again&#8230;</p>
<p>If the water flow does not look right to you <strong></strong>(and you obviously have been watching it since new<strong></strong>) then it is not right, and will continue to get worse&#8230;Changing the pump will not fix a thing unless the pump had a problem&#8230;It can only pump water thru unrestricted passages, and that water it can pump will re-direct to the un-restricted passages&#8230;Like said&#8230;Path of least resistance.</p>
<p>From descriptions here &amp; in the thread I started&#8230;It seems the 459 has what I would call a odd or improper A/C plumbing/pump setup&#8230;</p>
<p>This happens sometimes with boat builders&#8230;Generally speaking&#8230;In my experience the only way to get them to make a change in a poor setup is for enough customers to have a problem and complain&#8230;No amount of prodding from us A/C guys ever seems to help in effecting that change&#8230;It&#8217;s a shame too because we are the ones dealing with this stuff everyday&#8230;They deal with building boats everyday&#8230;</p>
<p>So what is the fix ?&#8230;Well marine growth will always be a problem but there are a few things that can be done to help&#8230;</p>
<p>Over the years the A/C systems that boat builders install have gravitated to the Self Contained all in one units as opposed to the Split/Remote systems that most utilised for years&#8230;They don&#8217;t need guys with refrigerant certification to install or buy these All in One units&#8230;They are easier to install, and freon leaks in connections of copper tubing line runs are no longer something they need to worry about warrantying&#8230;.All they have to do now is run power, water hoses from the pump, and duct&#8230;</p>
<p>The problem with this is the water runs are now much further than when the &#8220;Central&#8221; type systems were installed all in one location close to the pump&#8230;Back then we had very little growth problems <strong></strong>(just scale buildup in condensers that was easy to remove<strong></strong>) and flow was much easier to plan &amp; maintain&#8230;</p>
<p>What I have found since this change is that the further, and or higher you pump seawater&#8230;The more problems you will have with growth, and it has also created the problems I describe below with using larger pumps&#8230;</p>
<p>Directing a pumps flow to units of varying distance &amp; height for even flow to each&#8230;Is a challenge to say the least !<br /> Generally their answer is to install an oversized pump in an attempt to brute force flow&#8230;</p>
<p>No I have not seen a 459 but it has been described as having two units on the bridge and 2 down below&#8230;I don&#8217;t care how they manifold this setup&#8230;It still going to be very hard to get the proper flow to each unit, and the least little restriction can and will upset any kind of balance they have designed into that system&#8230;The Pump has to overcome the height <strong></strong>(Head<strong></strong>) it needs to pump to the units on the bridge so it likely has been over sized just to do that with enough volume for those units&#8230;The remaining water can then supply the lower units&#8230;</p>
<p>Over sized pumps are never really the best answer over time <strong></strong>(though it may be cheaper for them<strong></strong>) because a over sized pump attempting to pump thru say four 5/8&#8243; condensers <strong></strong>(in this case<strong></strong>) is <strong></strong>(even when the system is clean<strong></strong>) likely not pumping it&#8217;s rated flow which will cause it&#8217;s impeller to cavitate&#8230;This causes cavitation burns to the bronze impeller &amp; pump housing&#8230;Thus causing premature pump head failure.</p>
<p>Again having not seen the install&#8230;My answer would be to install two pumps&#8230;One for the upper units, and one for the lower units&#8230;<br /> They both could then be sized for the job presented, the systems &amp; pumps would be much happier with less overall maintenance.</p>
<p>Steve~</p>
</blockquote>
]]></content:encoded>