August 07, 2009 | Steve Pooler | Comments 5

Marine A/C Pumps and Pump Relays

Join the forum discussion on this post - (9) Posts

We have touched on seawater cooling and lack of…Now what about if you have a intermittent problem, or the pump won’t start at all ?

In boats with multiple systems running on one seawater pump there is most likely a Pump Relay to receive a signal from each system to tell the pump it needs to run…That is unless it has been bypassed and the pump runs 24/7 from the breaker ( I see this done fairly often)

Lets start with the breaker in the main panel…Most are labeled A/C pump or similar…Some boats may have the pump breaker tied in with one of the A/C system breakers (Ocean Yachts for one used to connect the pump to the Main Salon A/C Breaker) but most should have a stand alone breaker…

The breaker feeds the pump relay and carries the load of the pump only…this power can be either 115 or 230 volts depending on the pump installed…

The individual systems aboard will then have their own breaker that powers/protects each A/C system & it’s wiring…These can also be 115 or 230v supplied…The reason I describe this is that some boats have a mixture of system voltages…Hatteras for example, always supplied one of the smaller systems as 115v and the rest as 230v…They would then install a 115v pump so that if all that is available on the dock is 115v, you can still have at least one cabin of A/C for crew/kids while the owners/parents go to the resort for the night without starting the generator (Well this has always been my assumption and nowadays most docks will have 230v anyway)

There have been many types of pump relays over the years…Some with mechanical relays (in previous times) but most for many years have been “ignition protected” solid state designs…Here are the most current & popular versions that I see, and a few of the most common failures…

Some were for built for only 2 systems and could not be expanded for more…Marine Air still makes a 2 unit relay (2PRP) but they also offer one that can handle up to 6 systems (6PRP) on one pump…you don’t have to utilise all if you have say 3 or 4 systems, and it actually gives you spare circuits to re-connect a system to if the one it’s connected to were to fail (that is if you have the 6PRP)…These relays are just a metal box with a single circuit board and all needed components on that board…Other than complete board replacement, there are no repair parts available/needed.

Cruisair went about it a bit differently…Years ago they offered one pump relay that could handle up to 8 systems on one pump (PR8X) and it came with individualised components, all of which could be replaced…The “Circuit Board” & separate” Triac” (solid state relay that switches & carries the pump current) came with the box…You could then add “Triggers” for as many units as needed, and you could also select trigger voltage (115 or 230) to match the system voltage feeding it….These triggers of course were/are replaceable with two screws & two plug on wires in the event of failure…

The only problem with this Pump Relay was the box was a bit large for smaller areas in boats that may only need 2 or three triggers…So they built a smaller box that can house all the same basic components (circuit board & triac) but only has room for up to 3 triggers…It can also be purchased with the triggers pre-installed for either 2 or 3 systems (PR3X-?) The question mark would be the number of triggers pre-installed (either 2 or 3)…They still offer the PR8X, and it can also now be purchased with triggers pre-installed but either box is not hard to add/install trigger/s in…

The main purpose of these relays is to run the pump when a system is calling for it…That means any system that is running a compressor (Some with just fan, IE: older Three knob cabin control-ed systems)…But if a trigger circuit in either type box fails (Marine Air, Cruisair, or any manufacturer) the pump may run for one or more systems…But not for the one that has the failed trigger circuit…

This sometimes causes confusion because if any one of the good triggers starts the pump…All systems that are connected to that pump will get seawater, and thus run normally….

However if the system/s with the good trigger/s cycle off, and the one with the bad trigger either continues to run, or starts up with the others off…It may/should shut down randomly with a fault code on the cabin display.

The easiest thing to do to verify if you have a problem is to test run each system” individually” to verify if you are pumping water with just that system running…If you find a system that won’t start the pump, the trigger circuit (in the pump relay) for that system has likely failed.

Also if the pump won’t run at all…These Pump Relays all have fuses installed either inside the box (Newer automotive type pull out fuse) or in a typical twist type fuse holder mounted thru the box ( It’s how Ocean Yachts gets away with running the pump on the salon breaker)…This should be one of the first things to check….If the fuse is blown, and then blows again after replacement, it’s time to look at the pump & associated wiring for shorts or bad/wet connections.

These Pumps & Relays are pretty easy to troubleshoot with a volt meter and a bit of common sense, but going into that here would be a bit long for all models…If you want help with your individual installation, I’ll be more that happy to answer in the forum troubleshooting section http://marine-ac.com/forum/troubleshooting/

Just let me know what you have and we can solve it there together…If you have another brand of equipment or model of pump relay, it’s likely that I have seen a few…We can figure those out together too…

Steve~

Entry Information

Filed Under: AC/SystemsMaintence TipsPumps & Pump Relays

Tags:

About the Author: Steve Pooler is a marine air conditioning specialist based on the West Coast of Florida. His marine repair background started in the 1970's at a family owned and operated boat yard in St Petersburg, Florida. Steve has a knowledge of most all specialties involved with marine and yacht repair. For the last 20 years (11 of which were for a Cruisair distributor) Steve's specialty has been yacht & boat air conditioning and refrigeration service.

RSSComments: 5  |  Post a Comment  |  Trackback URL

  1. called steve on the phone..answered on first ring. He answered all my questions I had on my a/c pump relay. Thanks for the prompt and friendly service you provided.

  2. This is a recent e-mail to Marine-A/C.com from Dave:
    Message: i have 2 a/c units on my 1990 35′ searay. When I put my #1 unit breaker tn on my ac water pump turns on even if the unit is not running . Shut that switch off and turn on the other switch it will not start the a/c pump at all. Is it time for a new pump relay box or can I have the pump relay rebuild or ???

  3. I tried to respond directly to Dave 3 times, but keep getting the mails back as no such address, or they didn’t like the sender…Who Me ?

    If you are out there Dave…I’m trying…
    Please join the forum…We can further discuss your issue there…

    Below is copy of my response to his mail:

    Hi Dave,

    Yes pump relays can be repaired but…

    Your Sea Ray being a 1990 model…There could have been a replacement pump relay installed during that time…

    Depending on the repair man’s parts availability it could be a Marine Air or other manufacture replacement.

    To know which relay it was, or was not replaced with, would be hard for me to say…I really need a pump relay model # to help. (it’s on the front cover of the pump relay box)

    Also…I need to know if you have digital or manual (3 knob controls)…and if there is a separate seawater pump relay breaker in the main panel…

    Those answers can affect how it is all “supposed” to work….

    It could be that the pump relay is wired to the #1 A/C breaker (as opposed to it’s own breaker)…and that breaker will always need to be ON regardless of if you are using #1 A/C or not
    (To power the pump relay & pump)

    It could also be that the existing pump relay has been bypassed, and or, the pump is now connected directly to the #1 A/C breaker.
    (That’s the reason it would help to know the type of controls you have)

    Manual controls ran the pump with either fan 24/7…Digitals run the pump only if a compressor is running (either compressor, or both)

    I would prefer to talk about all this in the Forum where others can benefit from the answers as well….

    Steve~

  4. I have a PR3X-2C with three A/C units. The pump does not run for any of the three A/C. Voltage to the pump relay is 240 for all three units. Output from the relay is zero. Have bypassed the pump relay and the pump runs so I can run it using the pump breaker. I understand the relay is a replaceable item but don’t see it listed on your web page. Would appreciate info on how to order. Larry Roesler

  5. Hi Larry…The best thing to do here is either call me, or register in the Forum section & ask there…

    There are a few things to check to determine what has failed…BTW if you have three 230 volt systems…It should be a PR3X-3C…3C being for three 230 volt triggers.

"Please submit your comments and questions on our Marine-AC Forum"